ApprovedFiled Jan 12, 2026 by Emerson Stroud, Keystone Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Jan 12, 2026
- Assembly type
- RP
- Serial number
- K348905
- Size
- 1
- Test gauge serial
- G-2763
- Gauge calibration date
- Nov 17, 2025
- Check valve 1
- 3.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.9 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Emerson Stroud, current on the service date
- All required fields present
- Address matches parcel 067-70-01241
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
6928 Laurel Ln
Owner: Wexler Holdings LLC
Parcel 067-70-01241