Back to the backflow review queue

Backflow assembly test: Hilltop Diner

Approved

Filed Jan 12, 2026 by Emerson Stroud, Keystone Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jan 12, 2026
Assembly type
RP
Serial number
K348905
Size
1
Test gauge serial
G-2763
Gauge calibration date
Nov 17, 2025
Check valve 1
3.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Stroud, current on the service date
  • All required fields present
  • Address matches parcel 067-70-01241
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6928 Laurel Ln
Owner: Wexler Holdings LLC
Parcel 067-70-01241