Back to the backflow review queue

Backflow assembly test: 671 Hickory Trl

Approved

Filed Jul 26, 2026 by Avery Benton, Keystone Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jul 26, 2026
Assembly type
RP
Serial number
A127274
Size
1
Test gauge serial
G-2421
Gauge calibration date
Oct 2, 2025
Check valve 1
7.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Benton, current on the service date
  • All required fields present
  • Address matches parcel 067-95-01176
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

671 Hickory Trl
Owner: Alex Benton
Parcel 067-95-01176