Backflow assembly test: 6665 Turkey Hill Trl

Approved

Filed Jun 18, 2025 by Avery Benton, Keystone Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 18, 2025
Assembly type
RP
Serial number
B191535
Size
1
Test gauge serial
G-8438
Gauge calibration date
Mar 19, 2025
Check valve 1
3.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Benton, current on the service date
  • All required fields present
  • Address matches parcel 067-61-01286
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

6665 Turkey Hill Trl
Owner: Cameron Whitcomb
Parcel 067-61-01286