Back to the backflow review queue

Backflow assembly test: 342 Stone Gate Rd

Approved

Filed Jun 14, 2024 by Quinn Wexler, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 14, 2024
Assembly type
PVB
Serial number
K261766
Size
3/4
Test gauge serial
G-3893
Gauge calibration date
Oct 6, 2023
Check valve 1
9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Wexler, current on the service date
  • All required fields present
  • Address matches parcel 067-53-01031
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

342 Stone Gate Rd
Owner: Taylor Vance
Parcel 067-53-01031