Backflow assembly test: Hilltop Medical Offices

Filed Nov 27, 2026 by Quinn Wexler, Lakeside Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Nov 27, 2026
Assembly type
RP
Serial number
B315544
Size
4
Test gauge serial
G-2707
Gauge calibration date
Aug 23, 2026
Check valve 1
4.3 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Wexler, current on the service date
  • All required fields present
  • Address matches parcel 067-49-01175
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Property

2652 Cedar Hollow Way
Owner: Danner Holdings LLC
Parcel 067-49-01175