Back to the backflow review queue
Backflow assembly test: Hilltop Medical Offices
Needs reviewFiled Nov 27, 2026 by Quinn Wexler, Lakeside Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Nov 27, 2026
- Assembly type
- RP
- Serial number
- B315544
- Size
- 4
- Test gauge serial
- G-2707
- Gauge calibration date
- Aug 23, 2026
- Check valve 1
- 4.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.2 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Wexler, current on the service date
- All required fields present
- Address matches parcel 067-49-01175
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
2652 Cedar Hollow Way
Owner: Danner Holdings LLC
Parcel 067-49-01175