Backflow assembly test: 4226 Stone Gate Ln

Approved

Filed Nov 19, 2025 by Quinn Wexler, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 19, 2025
Assembly type
RP
Serial number
A723330
Size
3/4
Test gauge serial
G-7495
Gauge calibration date
Jun 21, 2025
Check valve 1
5.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Relief valve opened at
4.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Wexler, current on the service date
  • All required fields present
  • Address matches parcel 067-65-01348
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4226 Stone Gate Ln
Owner: Hayden Benton
Parcel 067-65-01348