Back to the backflow review queue

Backflow assembly test: 130 Spring Branch Way

Approved

Filed Mar 4, 2025 by Reese Danner, Keystone Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Mar 4, 2025
Assembly type
RP
Serial number
A296262
Size
3/4
Test gauge serial
G-1819
Gauge calibration date
Oct 3, 2024
Check valve 1
4.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Danner, current on the service date
  • All required fields present
  • Address matches parcel 067-45-01173
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

130 Spring Branch Way
Owner: Parker Vance
Parcel 067-45-01173