Backflow assembly test: 130 Spring Branch Way

Approved

Filed Mar 20, 2026 by Quinn Wexler, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Mar 20, 2026
Assembly type
RP
Serial number
A296262
Size
3/4
Test gauge serial
G-3676
Gauge calibration date
Feb 26, 2025
Check valve 1
0.5 psid
Check valve 1 closed tight
No
Check valve 2
1.9 psid
Relief valve opened at
2.9 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Wexler, current on the service date
  • All required fields present
  • Address matches parcel 067-45-01173
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

130 Spring Branch Way
Owner: Parker Vance
Parcel 067-45-01173