Backflow assembly test: 5339 Mill Creek Dr

Approved

Filed Mar 5, 2025 by Quinn Wexler, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Mar 5, 2025
Assembly type
RP
Serial number
B634172
Size
1
Test gauge serial
G-1560
Gauge calibration date
Dec 25, 2024
Check valve 1
8.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Wexler, current on the service date
  • All required fields present
  • Address matches parcel 067-59-01292
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.