Backflow assembly test: 4750 Cedar Hollow Ct
ApprovedFiled Jan 10, 2025 by Quinn Wexler, Lakeside Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jan 10, 2025
- Assembly type
- DC
- Serial number
- Z726547
- Size
- 3/4
- Test gauge serial
- G-7826
- Gauge calibration date
- May 30, 2024
- Check valve 1
- 3.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Wexler, current on the service date
- All required fields present
- Address matches parcel 067-25-01135
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
4750 Cedar Hollow Ct
Owner: Logan Wexler
Parcel 067-25-01135