Back to the backflow review queue

Backflow assembly test: 8550 Mill Creek Ct

Approved

Filed Oct 24, 2026 by Reese Danner, Keystone Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 24, 2026
Assembly type
RP
Serial number
K593893
Size
1
Test gauge serial
G-2128
Gauge calibration date
Sep 16, 2026
Check valve 1
6.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Danner, current on the service date
  • All required fields present
  • Address matches parcel 067-88-01061
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8550 Mill Creek Ct
Owner: Casey Whitcomb
Parcel 067-88-01061