Backflow assembly test: 5200 Spring Branch Ln

Approved

Filed Feb 11, 2026 by Reese Danner, Keystone Plumbing & Backflow. Filed from a phone.

Report

Date of service
Feb 11, 2026
Assembly type
DC
Serial number
W423810
Size
3/4
Test gauge serial
G-5398
Gauge calibration date
Jan 10, 2025
Check valve 1
7.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Danner, current on the service date
  • All required fields present
  • Address matches parcel 067-43-01035
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.