Backflow assembly test: 6462 Mill Creek Way
ApprovedFiled Aug 14, 2025 by Avery Benton, Keystone Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Aug 14, 2025
- Assembly type
- PVB
- Serial number
- W937226
- Size
- 1
- Test gauge serial
- G-1110
- Gauge calibration date
- Apr 30, 2025
- Check valve 1
- 8.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Benton, current on the service date
- All required fields present
- Address matches parcel 067-45-01343
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
6462 Mill Creek Way
Owner: Parker Okafor
Parcel 067-45-01343