Back to the backflow review queue

Backflow assembly test: 5114 Fox Run Ln

Approved

Filed Aug 25, 2025 by Avery Whitcomb, Keystone Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Aug 25, 2025
Assembly type
RP
Serial number
A529005
Size
1
Test gauge serial
G-8757
Gauge calibration date
Dec 16, 2024
Check valve 1
8.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 071-41-01235
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5114 Fox Run Ln
Owner: Cameron Okafor
Parcel 071-41-01235