Backflow assembly test: 6332 Ridgeview Ct

Approved

Filed Jul 15, 2026 by Jordan Vance, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jul 15, 2026
Assembly type
RP
Serial number
K896713
Size
3/4
Test gauge serial
G-9658
Gauge calibration date
Feb 5, 2026
Check valve 1
5.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jordan Vance, current on the service date
  • All required fields present
  • Address matches parcel 071-69-01108
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.