Back to the backflow review queue

Backflow assembly test: 7590 Orchard Trl

Approved

Filed May 3, 2024 by Jordan Vance, Heritage Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
May 3, 2024
Assembly type
RP
Serial number
K123796
Size
1
Test gauge serial
G-3405
Gauge calibration date
Aug 6, 2023
Check valve 1
5.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jordan Vance, current on the service date
  • All required fields present
  • Address matches parcel 071-54-01034
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7590 Orchard Trl
Owner: Riley Brandt
Parcel 071-54-01034