Back to the backflow review queue
Backflow assembly test: 8067 Turkey Hill Dr
ApprovedFiled Aug 22, 2024 by Drew Hollins, Summit Backflow Testing. Filed from a phone.
Report
- Date of service
- Aug 22, 2024
- Assembly type
- DC
- Serial number
- W278351
- Size
- 3/4
- Test gauge serial
- G-4932
- Gauge calibration date
- Feb 11, 2024
- Check valve 1
- 5.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Hollins, current on the service date
- All required fields present
- Address matches parcel 071-82-01176
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
8067 Turkey Hill Dr
Owner: Hayden Marsh
Parcel 071-82-01176