Backflow assembly test: 8067 Turkey Hill Dr
ApprovedFiled Sep 24, 2025 by Quinn Okafor, Heritage Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Sep 24, 2025
- Assembly type
- DC
- Serial number
- W278351
- Size
- 3/4
- Test gauge serial
- G-4238
- Gauge calibration date
- Jul 16, 2025
- Check valve 1
- 4.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Okafor, current on the service date
- All required fields present
- Address matches parcel 071-82-01176
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
8067 Turkey Hill Dr
Owner: Hayden Marsh
Parcel 071-82-01176