Backflow assembly test: 4417 Hickory Dr
ApprovedFiled Sep 27, 2024 by Drew Hollins, Summit Backflow Testing. Filed from a phone.
Report
- Date of service
- Sep 27, 2024
- Assembly type
- RP
- Serial number
- Z435394
- Size
- 1
- Test gauge serial
- G-5925
- Gauge calibration date
- Jan 20, 2024
- Check valve 1
- 7.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.2 psid
- Relief valve opened at
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Hollins, current on the service date
- All required fields present
- Address matches parcel 071-96-01203
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
4417 Hickory Dr
Owner: Alex Pruitt
Parcel 071-96-01203