ApprovedFiled Jul 2, 2026 by Hayden Danner, Keystone Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jul 2, 2026
- Assembly type
- RP
- Serial number
- W833798
- Size
- 1
- Test gauge serial
- G-5748
- Gauge calibration date
- Oct 29, 2025
- Check valve 1
- 8.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Danner, current on the service date
- All required fields present
- Address matches parcel 071-74-01014
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.