Backflow assembly test: Two Rivers Car Wash

Approved

Filed Aug 26, 2026 by Blake Danner, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Aug 26, 2026
Assembly type
DC
Serial number
A420882
Size
1
Test gauge serial
G-9520
Gauge calibration date
Mar 26, 2026
Check valve 1
0.6 psid
Check valve 1 closed tight
No
Check valve 2
2.6 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Danner, current on the service date
  • All required fields present
  • Address matches parcel 071-67-01095
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

1465 Spring Branch Ct
Owner: Vance Holdings LLC
Parcel 071-67-01095