Backflow assembly test: 3796 Cedar Hollow Trl
ApprovedFiled Nov 30, 2025 by Jordan Vance, Heritage Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Nov 30, 2025
- Assembly type
- DC
- Serial number
- B711858
- Size
- 1
- Test gauge serial
- G-5542
- Gauge calibration date
- Aug 5, 2025
- Check valve 1
- 5.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.9 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jordan Vance, current on the service date
- All required fields present
- Address matches parcel 071-62-01349
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.