Backflow assembly test: 105 Old Church Ln
ApprovedFiled Jul 9, 2024 by Hayden Danner, Keystone Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jul 9, 2024
- Assembly type
- DC
- Serial number
- Z567574
- Size
- 3/4
- Test gauge serial
- G-1089
- Gauge calibration date
- Jun 11, 2023
- Check valve 1
- 0.5 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.3 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Danner, current on the service date
- All required fields present
- Address matches parcel 071-27-01051
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
105 Old Church Ln
Owner: Quinn Whitcomb
Parcel 071-27-01051