Back to the backflow review queue
Backflow assembly test: 8918 Mill Creek Rd
ApprovedFiled Jul 16, 2024 by Hayden Danner, Keystone Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jul 16, 2024
- Assembly type
- RP
- Serial number
- B395485
- Size
- 1
- Test gauge serial
- G-1942
- Gauge calibration date
- May 30, 2024
- Check valve 1
- 6.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.2 psid
- Relief valve opened at
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Danner, current on the service date
- All required fields present
- Address matches parcel 071-50-01308
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
8918 Mill Creek Rd
Owner: Parker Ramirez
Parcel 071-50-01308