Back to the backflow review queue

Backflow assembly test: Corner Diner

Approved

Filed Jun 2, 2024 by Jordan Vance, Heritage Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jun 2, 2024
Assembly type
RP
Serial number
K715436
Size
1 1/2
Test gauge serial
G-3829
Gauge calibration date
Apr 28, 2024
Check valve 1
4.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jordan Vance, current on the service date
  • All required fields present
  • Address matches parcel 071-94-01066
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1392 Cedar Hollow Rd
Owner: Hollins Holdings LLC
Parcel 071-94-01066