Backflow assembly test: 5084 Hickory Dr
ApprovedFiled Jul 13, 2025 by Rowan Kessler, Valley Backflow Testing. Filed from a phone.
Report
- Date of service
- Jul 13, 2025
- Assembly type
- RP
- Serial number
- Z773509
- Size
- 3/4
- Test gauge serial
- G-3065
- Gauge calibration date
- Feb 20, 2025
- Check valve 1
- 4.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Rowan Kessler, current on the service date
- All required fields present
- Address matches parcel 073-23-01297
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.