Backflow assembly test: 7398 Old Church Trl

Approved

Filed Jan 5, 2026 by Logan Vance, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Jan 5, 2026
Assembly type
RP
Serial number
A215740
Size
3/4
Test gauge serial
G-8004
Gauge calibration date
May 6, 2025
Check valve 1
3.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Vance, current on the service date
  • All required fields present
  • Address matches parcel 073-39-01092
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7398 Old Church Trl
Owner: Morgan Calloway
Parcel 073-39-01092