Back to the backflow review queue

Backflow assembly test: 8108 Sycamore Rd

Approved

Filed Oct 18, 2026 by Parker Fairley, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Oct 18, 2026
Assembly type
PVB
Serial number
A340858
Size
1
Test gauge serial
G-6410
Gauge calibration date
Mar 3, 2026
Check valve 1
5.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Fairley, current on the service date
  • All required fields present
  • Address matches parcel 073-48-01269
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8108 Sycamore Rd
Owner: Emerson Fairley
Parcel 073-48-01269