Backflow assembly test: Hilltop Self Storage

Approved

Filed Jun 29, 2024 by Parker Fairley, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Jun 29, 2024
Assembly type
RP
Serial number
Z748808
Size
4
Test gauge serial
G-4791
Gauge calibration date
Feb 6, 2024
Check valve 1
6.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Fairley, current on the service date
  • All required fields present
  • Address matches parcel 073-95-01296
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.