Backflow assembly test: Hilltop Self Storage

Approved

Filed Jul 31, 2025 by Parker Okafor, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Jul 31, 2025
Assembly type
RP
Serial number
Z748808
Size
4
Test gauge serial
G-7177
Gauge calibration date
Jan 16, 2025
Check valve 1
5.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Okafor, current on the service date
  • All required fields present
  • Address matches parcel 073-95-01296
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.