Back to the backflow review queue

Backflow assembly test: Hilltop Self Storage

Approved

Filed Aug 26, 2026 by Parker Okafor, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Aug 26, 2026
Assembly type
RP
Serial number
Z748808
Size
4
Test gauge serial
G-4488
Gauge calibration date
Jan 30, 2026
Check valve 1
5.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Okafor, current on the service date
  • All required fields present
  • Address matches parcel 073-95-01296
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

3470 Laurel Way
Owner: Brandt Holdings LLC
Parcel 073-95-01296