Backflow assembly test: Two Rivers Animal Hospital
ApprovedFiled Oct 31, 2025 by Rowan Kessler, Valley Backflow Testing. Filed from a phone.
Report
- Date of service
- Oct 31, 2025
- Assembly type
- RP
- Serial number
- A787694
- Size
- 1 1/2
- Test gauge serial
- G-2109
- Gauge calibration date
- May 2, 2025
- Check valve 1
- 6.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Rowan Kessler, current on the service date
- All required fields present
- Address matches parcel 073-31-01061
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.