Back to the backflow review queue
Backflow assembly test: 6479 Spring Branch Trl
ApprovedFiled Sep 20, 2025 by Parker Fairley, Heritage Backflow Testing. Filed from a phone.
Report
- Date of service
- Sep 20, 2025
- Assembly type
- DC
- Serial number
- W487901
- Size
- 3/4
- Test gauge serial
- G-8568
- Gauge calibration date
- Nov 18, 2024
- Check valve 1
- 0.5 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.8 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Fairley, current on the service date
- All required fields present
- Address matches parcel 073-16-01345
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
6479 Spring Branch Trl
Owner: Alex Whitcomb
Parcel 073-16-01345