Backflow assembly test: 1220 Spring Branch Trl

Approved

Filed Jul 27, 2024 by Parker Okafor, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Jul 27, 2024
Assembly type
RP
Serial number
K907534
Size
3/4
Test gauge serial
G-7127
Gauge calibration date
May 30, 2024
Check valve 1
3.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Okafor, current on the service date
  • All required fields present
  • Address matches parcel 073-44-01100
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1220 Spring Branch Trl
Owner: Logan Fairley
Parcel 073-44-01100