Back to the backflow review queue

Backflow assembly test: Golden Pizza

Approved

Filed Dec 14, 2025 by Rowan Kessler, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Dec 14, 2025
Assembly type
RP
Serial number
W586209
Size
1
Test gauge serial
G-8233
Gauge calibration date
Mar 10, 2025
Check valve 1
6.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Kessler, current on the service date
  • All required fields present
  • Address matches parcel 073-67-01332
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

672 Laurel Ln
Owner: Marsh Holdings LLC
Parcel 073-67-01332