Backflow assembly test: Station Animal Hospital

Approved

Filed Oct 26, 2026 by Logan Vance, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Oct 26, 2026
Assembly type
RP
Serial number
A937891
Size
1 1/2
Test gauge serial
G-5654
Gauge calibration date
May 19, 2026
Check valve 1
7.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Vance, current on the service date
  • All required fields present
  • Address matches parcel 073-24-01307
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

8995 Meadow Lark Ln
Owner: Nguyen Holdings LLC
Parcel 073-24-01307