Backflow assembly test: 8012 Meadow Lark Ln
ApprovedFiled May 3, 2026 by Parker Fairley, Heritage Backflow Testing. Filed from a phone.
Report
- Date of service
- May 3, 2026
- Assembly type
- RP
- Serial number
- K637303
- Size
- 1
- Test gauge serial
- G-1967
- Gauge calibration date
- Sep 13, 2025
- Check valve 1
- 3.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.4 psid
- Relief valve opened at
- 2.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Fairley, current on the service date
- All required fields present
- Address matches parcel 073-21-01259
- Readings in range, no flags
- Result: passing. Next due date resets when approved.