Backflow assembly test: Blue Heron Taqueria

Approved

Filed Mar 28, 2025 by Logan Vance, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Mar 28, 2025
Assembly type
DC
Serial number
Z685560
Size
1 1/2
Test gauge serial
G-7000
Gauge calibration date
Jun 14, 2024
Check valve 1
4.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Vance, current on the service date
  • All required fields present
  • Address matches parcel 073-74-01104
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.