Backflow assembly test: 4542 Hickory Ln

Approved

Filed Jun 16, 2025 by Logan Vance, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Jun 16, 2025
Assembly type
PVB
Serial number
A295660
Size
1
Test gauge serial
G-6726
Gauge calibration date
Oct 13, 2024
Check valve 1
5.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Vance, current on the service date
  • All required fields present
  • Address matches parcel 073-67-01204
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.