Backflow assembly test: Main Street Pizza
ApprovedFiled Oct 10, 2026 by Rowan Kessler, Valley Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Oct 10, 2026
- Assembly type
- RP
- Serial number
- Z375278
- Size
- 1
- Test gauge serial
- G-9330
- Gauge calibration date
- Apr 11, 2026
- Check valve 1
- 8.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Relief valve opened at
- 2.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Rowan Kessler, current on the service date
- All required fields present
- Address matches parcel 073-68-01056
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
4519 Sycamore Trl
Owner: Kessler Holdings LLC
Parcel 073-68-01056