Back to the backflow review queue

Backflow assembly test: 7265 Stone Gate Ct

Approved

Filed Jan 16, 2026 by Rowan Kessler, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Jan 16, 2026
Assembly type
RP
Serial number
Z194472
Size
3/4
Test gauge serial
G-3476
Gauge calibration date
Dec 5, 2025
Check valve 1
3.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Kessler, current on the service date
  • All required fields present
  • Address matches parcel 073-93-01196
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7265 Stone Gate Ct
Owner: Avery Hollins
Parcel 073-93-01196