Back to the backflow review queue
Backflow assembly test: 2941 Meadow Lark Way
ApprovedFiled Aug 29, 2026 by Parker Fairley, Heritage Backflow Testing. Filed from a phone.
Report
- Date of service
- Aug 29, 2026
- Assembly type
- PVB
- Serial number
- K125344
- Size
- 3/4
- Test gauge serial
- G-9851
- Gauge calibration date
- Jan 24, 2026
- Check valve 1
- 3.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Fairley, current on the service date
- All required fields present
- Address matches parcel 073-70-01193
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
2941 Meadow Lark Way
Owner: Morgan Nguyen
Parcel 073-70-01193