Backflow assembly test: Main Street Bakery

Approved

Filed Apr 8, 2025 by Logan Vance, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Apr 8, 2025
Assembly type
RP
Serial number
W838904
Size
4
Test gauge serial
G-4714
Gauge calibration date
Jul 9, 2024
Check valve 1
4.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Vance, current on the service date
  • All required fields present
  • Address matches parcel 073-74-01068
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.