Back to the backflow review queue

Backflow assembly test: Crossroads Grill

Approved

Filed Mar 9, 2026 by Parker Okafor, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Mar 9, 2026
Assembly type
RP
Serial number
K999092
Size
1
Test gauge serial
G-4851
Gauge calibration date
Dec 29, 2025
Check valve 1
6.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Okafor, current on the service date
  • All required fields present
  • Address matches parcel 073-94-01045
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2627 Meadow Lark Way
Owner: Pruitt Holdings LLC
Parcel 073-94-01045