Backflow assembly test: Blue Heron Diner

Filed Nov 24, 2026 by Parker Fairley, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Nov 24, 2026
Assembly type
RP
Serial number
Z525602
Size
4
Test gauge serial
G-3295
Gauge calibration date
Oct 4, 2026
Check valve 1
3.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Relief valve opened at
1 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Fairley, current on the service date
  • All required fields present
  • Address matches parcel 073-84-01213
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.