Back to the backflow review queue
Backflow assembly test: Corner Brewing Co
ApprovedFiled Dec 14, 2024 by Rowan Kessler, Valley Backflow Testing. Filed from a phone.
Report
- Date of service
- Dec 14, 2024
- Assembly type
- DC
- Serial number
- W851761
- Size
- 4
- Test gauge serial
- G-7731
- Gauge calibration date
- Sep 4, 2024
- Check valve 1
- 4.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Rowan Kessler, current on the service date
- All required fields present
- Address matches parcel 073-72-01320
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
1294 Laurel Way
Owner: Pruitt Holdings LLC
Parcel 073-72-01320