Backflow assembly test: 1757 Sycamore Dr

Approved

Filed Feb 24, 2025 by Blake Pruitt, Patriot Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Feb 24, 2025
Assembly type
PVB
Serial number
Z590559
Size
1
Test gauge serial
G-9393
Gauge calibration date
Sep 4, 2024
Check valve 1
0.7 psid
Check valve 1 closed tight
No
Check valve 2
3.5 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 075-99-01010
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

1757 Sycamore Dr
Owner: Jamie Lindqvist
Parcel 075-99-01010