Back to the backflow review queue

Backflow assembly test: Station Diner

Approved

Filed Sep 6, 2025 by Jordan Wexler, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 6, 2025
Assembly type
RP
Serial number
B768749
Size
1 1/2
Test gauge serial
G-8001
Gauge calibration date
Nov 17, 2024
Check valve 1
5.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jordan Wexler, current on the service date
  • All required fields present
  • Address matches parcel 075-20-01029
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

8344 Mill Creek Trl
Owner: Ramirez Holdings LLC
Parcel 075-20-01029