Backflow assembly test: 1665 Stone Gate Dr

Approved

Filed Oct 12, 2025 by Alex Wexler, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Oct 12, 2025
Assembly type
PVB
Serial number
A266184
Size
1
Test gauge serial
G-7154
Gauge calibration date
Jan 29, 2025
Check valve 1
6.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Wexler, current on the service date
  • All required fields present
  • Address matches parcel 075-47-01178
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.