Backflow assembly test: 1589 Hickory Way
ApprovedFiled Oct 23, 2025 by Quinn Stroud, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 23, 2025
- Assembly type
- DC
- Serial number
- A761349
- Size
- 1
- Test gauge serial
- G-9270
- Gauge calibration date
- Jul 21, 2025
- Check valve 1
- 8.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Stroud, current on the service date
- All required fields present
- Address matches parcel 075-58-01062
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
1589 Hickory Way
Owner: Taylor Harlow
Parcel 075-58-01062